Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
124/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
O2 Module User x
Actual O2 Value Actual O2 value 0...100 % User --- x
O2 Setpoint O2 setpoint 0...25 % User --- x
SupplyAirTemp Supply air temperature in °C -100...923 °C User --- x
FlueGas Temp Flue gas temperature in °C -100...923 °C User --- x
CombEfficiency Combustion efficiency 0...200 % User --- x
BurnerID Identification of burner 4..15 characters User invalid x x
OptgModeSe-
lect
Operating mode selection of AZL5... for serial port and eBus User x x
InterfacePC Setting the serial port (RS-232) of the AZL5... to interface op-
eration for PC tool
User x x
GatewayBASon Activating the eBus port on the AZL5... for BAS User x x
GatewayBASoff Deactivating the eBus port on the AZL5... User x x
Type of Gateway eBus
Modbus
User Modbus x x
O2Ctrl activate Activating the O2 trim controller deactivated
activated
User --- x
ManualOperation Menu level for activating manual operation with the prese-
lected load
User x x
SetLoad Set target load 0..100%, S1, S2, S3 User --- x x
Autom/Manual/O
ff
Selection of manual or automatic operation Automatic
Burner on
Burner off
User Automatic x x
Params & Display Menu level for making the parameter settings User x x
BurnerControl Setting the burner control parameters User x x
Times Service x x
TimesStartup1 Burner control startup times 1 Service x x
MinTmeStartRel Minimum time for start release 0.2..63 s OEM 1 s x x
FanRunupTme Fan runup time 0.2..63 s OEM 2 s x x
PrepurgeT-
meGas
Prepurge time gas MinT_PrepurgeGas..63
min
Service 20 s x x
PrepurgeTmeOil Prepurge time oil MinT_PrepurgeOil..63 min Service 15 s x x
MinT_PrepurgeG
as
Minimum prepurge time gas 0.2..63 min OEM 20 s x x
MinT_PrepurgeO
il
Minimum prepurge time oil 0.2..63 min OEM 15 s x x