Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
126/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
Configuration USER x x
ConfigGeneral General parameters of burner control Service x x
AlarmStartPrev With / without alarm in the event of start prevention and heat
demand
deactivated
activated
Service deactivated x x
NormDirectStart Normal / direct start in the event of heat demand in phase 78 NormalStart
DirectStart
OEM NormalStart x x
OilPumpCou-
pling
Configuration for coupling the oil pump Magnetcoupl
Directcoupl
OEM Magnet-
coupl
x x
IgnOilPumpStart Switch-on time of ignition and oil pump on in Ph38
on in Ph22
OEM on in Ph38 x x
ForcedIntermit With / without forced intermittent operation deactivated
activated
Service activated x x
Continu-
ousPurge
Configuration for normal or continuous fan operation deactivated
activated
OEM deactivated x x
FuelTrainGas Fuel train when firing on gas DirectIgniG
Pilot Gp1
Pilot Gp2
OEM invalid x x
FuelTrainOil Fuel train when firing on oil LightOilLO
HeavyOilHO
LO w Gasp
HO w Gasp
OEM invalid x x
FuelTrainReset Resetting the fuel train to invalid value OEM x x
FuelTrainGas OEM x x
FuelTrainOil OEM x x
ContPilotGas Continuous pilot gas deactivated
activated
OEM deactivated x
ContPilotOil Continuous pilot oil deactivated
activated
OEM deactivated x
MainsFrequency Selection of mains frequency 50 / 60 Hz 50 Hz
60 Hz
OEM 50 Hz x x
ConfigIn/Output Configuring the inputs and outputs OEM x x
StartReleaseGas Input start release gas active deactivated
StartRelGas
CPI Gas
CPI Gas + Oil
CPI Oil
OEM StartRelGas x