169/301 
Siemens Building Technologies  Basic Documentation LMV5...  CC1P7550en 
HVAC Products  8 Commissioning instructions for the LMV5... system  13.08.2004 
 
 
Modulating burner with pressure control 
For the output step, any output value in % can be predefined. 100 % divided by the 
output step gives the number of possible steps. 
 
Parameters:  Shock protection on / off 
ColdStartOn 
activated 
  Shock protection activation level 
ThresholdOn 
40 % of setpoint 
  Output step (only for modulating opera-
tion) 
StageLoad 
10 % of burner output 
  Setpoint step modulating 
StageStep_Mod 
10 % of setpoint 
  Max. time modulating per step 
MaxTmeMod 
5 minutes 
  Shock protection deactivation level 
ThresholdOff 
80 % of setpoint 
 
Spacing of temperature lines
corresponds to the setpoint steps
from the actual setpoint, e.g. 10 % = 1 bar
Manipulated
variable
Actual value
Setpoint
Threshold OFF
Threshold ON
Load steps
e.g. 15 %
7550d30E/0502
10 bar = 100 %
8 bar = 80 %
7 bar
6 bar
5 bar
4 bar = 40 %
Load 85 %
Load 70 %
Load 55 %
Load 40 %
Burner start at
low-fire, e.g. 25 %
1. 2.
Burner off, 
actual value
below 
threshold ON.
Burner will be
switched on
Setpoint step not reached,
but max. time exceeded.
Therefore, increase of
manipulated variable  by
load step,
e.g. MaxTmeMod = 5 min.
Setpoint step is reached
before max. time has elapsed.
Increase of manipulated variable 
by load step.
⇒
Actual value reached.
Threshold OFF
Change to control
 
 
Menu level 1  Menu level 2  Menu level 3  Menu level 4  Menu level 5  Menu level 6 
Params & Display           
 
LoadController 
       
 
  ColdStart 
     
     
ColdStartOn 
ThresholdOn 
StageLoad 
StageStep_Mod 
StageStep_Stage 
MaxTmeMod 
MaxTmeStage 
ThresholdOff 
   
 
 
Example 
Example (cont’d)