LMVSeries TechnicalInstructions
 LV51000
SCCInc. Page50 Section3
DeaO2/Stp36 Energizing input X503.2 disables O
2
trim, while deenergizing X503.2 enables O
2
trim (LMV52 only).
EnergizinginputX503.3allowstheLMV5toprogresspastphase36.IfX503.3isdeenergized,theLMV5willremain
inphase36indefinitely.
CoolFctStbyThissettinghasnoeffect(LMV50only).
AutoDeactO2 Energizing input X503.3 will deactivate O2 trim by setting O2 trim OptgMode to auto deact.O2 trim
OptgModemustbesettoConAutoDeacforthisfunctiontowork.DeenergizingX503.3setstheO2trimOptgMode
backtoConAutoDeac.TerminalX503.2hasnofunctionwiththissetting.