TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section5 Page16SCCInc.
7. IfworkingonanunconfiguredLMV52,parametersunrelatedtotheVFDmustbesetbefore theVFD
canbestandardized.ThesearethoroughlyoutlinedinSection4under"Configuring
(Parameterizationof)anLMV5withaDefaultParameterSet".Tosummarize,thefollowingmustbe
set:burnerID,fueltrain,actuatoraddresses,actuatordirectionsofrotation,andactuatorspecial
positions.
8. TheLMV52safetyloopmustbeclosed(high
limit,lowwater,burnerflange,etc...)orthe
standardizationwillnotoccureveniftheLMV52isnotinalarm.
9. Theburnerswitchmustbeoff(LMV52inputX503.1mustbedeenergized).
10. TheVFDmustbeinremotemodesothatitwillrespecttherunstopconta
ctandtheanalogsignal
fromtheLMV52.
11. TheLMV52/VFD/blowerarenowreadytobestandardized.Thestandardization processcanbe
initiatedusingthefollowingmenupath:
Params&Display>VSDModule>Configuration>Speed>Standardization
SetparameterStandardizationto“activ
ated”.Theairdampershouldthendrivetotheprepurge
positionandtheVFD/blowershouldrampuptoapproximately60Hz(100%VFD).Afterafew
secondsat60Hz,theVFD/blowershouldrampbackdownto0Hz.Theairdampershouldalso
drivebacktohomeposition.
12. Checkthestandardizedspeed,whichistheproductofthestandar
dization,usingthefollowingmenu
path:
Params&Display>VSDModule>Configuration> Speed>StandardizedSp
For2polebl
owers,thestandardizedspeedshouldbe3500RPM,+/‐100RPM.Ifthespeedisoutof
thisrange,th
edrivewasmostlikelynotspannedsothat20mA=62Hz,orthemotorisheavily
loaded(alotofslip).Thesamelogicappliesto4polemotors,exceptthespeedshouldbe1700+/‐
100RPM.
13. IftheLMV52doesnothaveO
2
trim,theairdamperactuatorcanbesetbackto“activated”instead
of“airinfluen”usingthefo llowingmenupath:
Params&Display>RatioControl>Gas/OilSettings>AirActuator=activated
AdditionalTipsforBurnerswithVFDControl
Mostofthetime,speedfaultsthatareseenontheLMV52arecausedbytheVFDnotbeingableto
deceleratetheblowerwhentheblowerisbeingrampeddown.Iffastramptimesarenotcriticalfor
theapplication,ramptimescanbeincreasedandthisshouldcorrecttheissue.Iffastramptimes
arenecessary,abrakingresistormayalsoberequiredtoachievethefastrampdowntimes.