EasyManua.ls Logo

Siemens LMV52.440B1 - Open Circuit; Short Circuit Sensor Faults - Error Code A6 (Diagnostics 50

Siemens LMV52.440B1
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page9 Section7
OpenCircuit/ShortCircuitSensorFaultsErrorCodeA6(Diagnostics50…5A)
AnerrorcodeA6(diagnosticcode50…5A)meansthattheLMV5isconfiguredforacertaintype
ofsensor,butitisnotdetectingthatthesensorisconnected.Thismeansthataparameterin
theLMV5issetincorrectly,thewiringofthesensorisincorrect,orthesensorhasfailed.
Note:SomeofthefaultcodemessagesrefertoInput2orInput3.Input2isterminalX61
whichisusedforpressuresensors.Input3isterminalX62whichisusedforremotesetpoint
andmodulationsignals.
Checkthefollowing:
1. Ensurethattheparametersusedtoprogramtheanaloginputsaresetcorrectly:
LC_OptgMode
SensorSelect
ExtInpX61U/I
ExtInpX62U/I
SeeSection3forinformationonhowtheseparametersshouldbeset.
2. Ifalloftheaboveparametersaresetcorrectly,checkthewiringoftheattachedsensors.
SeeSection2forinformationonhowtowiresensorstotheLMV5.
3. Onasteamboiler,atemperaturesensorcanbeusedinadditiontothepressuresensorfor
the cold start function.If this is the case,checkthesettingof parameter AdditionalSens.
SeeSection3formoreinformationonhowtosetthisparameter.
4. AnadditionalFGRtemperaturesensorcanbeinstalledtoperformanFGRholdfunction.If
parameter FGRMode is set to “temperature”, “temp.contr.”, or “TCautoDeact”, an FGR
sensorisexpectedtobewiredintoterminalX60orX86,dependingonthesettingofFGR
sensor.IfthisparameterissettoX60,checkthatthesensoriswiredcorrectly.
5. IfO
2
trimisbeingused,anambientairtemperaturesensorcanbewiredintoterminalX60.
Check the setting of parameter AirTempX60PT1000.If this is set to activated, a Pt1000
temperaturesensorisexpectedtobewiredintoterminalX60.
HOME

Table of Contents

Other manuals for Siemens LMV52.440B1

Related product manuals