EasyManua.ls Logo

Siemens LMV52.440B1 - Suggested O 2 Trim Commissioning - Traditional Nozzle Mixing Burner with no or Low Percentage FGR (Typically LMV52.240)

Siemens LMV52.440B1
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page9 Section6
SuggestedO
2
TrimCommissioning‐TraditionalNozzleMixingBurnerwithNoorLow
PercentageFGR(TypicallyLMV52.240)
1. Thecommissi oningprocedureassumesthefollowing:
a. AllPreRequisitesforanLMV52systemwithO
2
trim(andVSDifequipped)havebeenmet
accordingtoSection4ofthisliterature.
b. TheRatioControlCurveshavebeencommissionedaccordingtoSection4ofthisliterature.
c. Section6ofthisliteraturehasbeenreadand un derstooduptothispoint.
2. AswasthecasefortheRatioControlCurvesinSection4,thesamefreespreadsheetcanalsobe
usedtoassistinthecommissioningoftheO
2
trim.ThisspreadsheetgraphicallyillustratestheO
2
curvesaswellasprovidesanorderlywaytorecordthedetailsofhowtheburnerwassetup.
Figure63:LMVxCurvesSpreadsheet
3. ThekeytocommissioningtheO
2
curvesquicklyandeasilyiscontainedintheRatioControlCurves.
Specifically,thefollowingmustbeachievedforeachpointontheRatioControl Curves(as
paraphrasedfromSection4ofthisliterature):
a. Safe,efficientcombustionasverifiedbyacalibratedstackgasanalyzer
b. The%loadmatchingthefuelflowwithin+/‐3%
c. Emissionscompliance
d. SmoothRatioControlCurves(nosharppeaksorvalleys)
e. VSDspeedshouldincreasewithloadinalinearfashion(ifequipped)
f. Findandreco
rdthe%O
2
wetcorrespondingtothefuelrichlimit(O2Alarmvalue)foreachpoint
byprobing.*
g. Findandrecordthe%O
2
wetcorrespondingtothefuelleanlimit(O2MaxValue)forPoint1and
Point10byprobing.*
h. Lastbutnotleast,leavethecurvepointssothatthe%O
2
wetis2%higherthanthefuelrichlimit
(O2Alarmvalue).Recordthisasthe"saved"valueforeachcurvepoint.
*NOTE:Whenprobingthefuelrichlimit,itisnotrecommendedtoexceed200PPMCO(drybasis)
orlessthan1.0%O
2
(wetordrybasis)foranypoint.Whenprobingthefuelleanlimit,itisnot
recommendedtoexceed200PPMCOoradverselyaffectflamestabilityforanypoint.
HOME

Table of Contents

Other manuals for Siemens LMV52.440B1

Related product manuals