c.  Whenactuatorisinstalledandcoupled,ensurethatallmountinghardwareistightened
adequately,andsomemethodofthreadlockingisemployedonthemountin ghardware
(exceptforthecouplinghardware).
d.  Ensureenvironmentalconditions(temperature,vibration, moisture,etc.)arenot
exceeded.
3.  Ensurethatallwiringispertheappli
cablewiringdiagramandalsomeetsapplicablelocaland
nationalcodes.Particularatten
tionshouldbepaidtothefollowing:
e.  Ifastep‐downcontroltransformeristhesourceof120VACpowerfortheLMV5,the
groundandneutralshouldbebonded(connected)onthetransformer.
f.  Voltagesupplytoa120VACLMV5mustbebetween102and132VAC,47‐63Hz.
Waveformmu
stbeafullsinewave.
g.  Thesmalltransformer(s)usedfortheLMV5(AGG5.210,typicallyblueorblack)mustbe
wiredandgrounded.SeeSection2(Wiring)formoredetails.Payattentiontopins3and
4onterminalSEK2andpropergrounding.IfmorethantwoSQM48andoneSQ
M45
actuatorsaremodulatedatthesametime,asecondtransformer(AGG5.210)willbe
required.
h.  CANbuswire(AGG5.643)mustbeused towirebetweenactuators.Plain,shieldedcable
isnotadequateandisnotpermitted.
i.  EnsurethatthelastdeviceandonlythelastdeviceontheCANbushasthetermination
jumperin
the“BusTermination”position.SeeSection2(Wiring)formoredetails.The
AZLhasbuilt‐intermination.
4.  Fuel(gas)supply mustbeadequatetosupporthighfireoperationandfuel(gas)trainmustbe
sizedcorrectly.
j.  Fuel(gas)pressurebeforethefiringratecontrolvalvemustbecorrect,stableand
repeatableatallfiringratesandmustnotvarywhenotherfuel(gas
)burningappliances
(otherboilersinthebuilding)arebeingoperated.
k.  Thefu
el(gas)pressureregulatorontheburnerbeingcommissionedshouldnotbefully
openathighfireandsho
uldnotbebouncingofftheseatatlowfire.Fuelregulator
mustbesizedproperly,andhaveadequateturndowncapability.
5.  AtemporarystackgasanalyzerthathasbeencalibratedandataminimumreadsO
2
(%)andCO
(ppm)mustbeusedforsettingcombustion.
6.  Knowledgeofwhatfuelflowrepresentshighfireoftheburner/boilercombinationandalsothe
turndownoftheburner/boiler combination.Thiscantypicallybefoundontheburner/boiler
nameplate.