LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page27 Section4
Parameter
% Value Notes
BoilerSetpointorSetpAddSensor N/A 300
o
F Currentsetpoint
ThresholdOn(%ofcurrentsetpoint) 50 150
o
F
Measuredtemperaturemustgobelow
ThresholdOntoengagecoldstart
ThresholdOff(%ofcurrentsetpoint) 80 240
o
F
Coldstartwillnotdisengageuntil
ThresholdOffismet
StageSetp_Mod(%ofcurrentsetpoint) 80 240
o
F
Definesthenecessarytemperature
changerequiredtotriggeraloadstep
StageLoad 5 N/A Determinesthesizeoftheloadstep
MaxTmeMod N/A 10min
Determinesthemax.timebetweenload
steps
Figure49:ExampleofaTimebasedSteppingStart