LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page13 Section6
Figure65:ExampleofTypicalLambdaFactorsforO
2
ControlCurvesinFigure64(above)
TheLambdaFactorcurvesserveasatooltoevaluatehowaccurateandrepeatablethefundamental
mechanicalsystemsoftheburnerareandhowwellallthecurveswerecommissioned.Ingeneral,the
LambdaFactorcurveshouldbeasconstantor"flat"aspossible.Theactualnumericalvalueisnot
important,buttheconsistencybetweenpointsis.Anapproximateguidefor
evaluationoftheLambda
Factor:
DifferenceinLambdaFactorbetweenadjacentpoints‐>lowernumbersarebetter.Max=0.35
(HighernumbersmayleadtoO
2
trimdeactivationsonsomeburnersduringmodulation).
StandardDeviationofallpointsonthecurve‐>lowernumbersarebetter.Max=0.30(Higher
numbersmayleadtoO
2
trimdeactivationsonsomeburnersduringmodulation).