EasyManua.ls Logo

Siemens LMV52.440B1 - Page 193

Siemens LMV52.440B1
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page21 Section6
O2MaxManVariableandO2MinManVariableTheseparameterssethowmuchtheO
2
systemcantrim
inanattempttoachievetheO
2
setpoint‐essentiallythetrimlimitsfortheO
2
system.
O2MaxManVariablesetshowmuchthesystemcanincreasetheairrate.Likewise,O2MinManVariable
setshowmuchthesystemcandecreasetheairrate.
Menupath:Params&Display>O2Contr/Alarm>GasSettings>ControlParam
ThesetrimlimitsmustbesetsothattheO
2
systemcanachievetheO
2
setpoint.However,thelimits
shouldnotbesetinawaythatallowstheburnertorunatanunsafefuelairratio.
Ideally,theO
2
trimsystemmustcompensatefortwomainenvironmentalconditions.Theseconditions
areambientairtemperatureandbarometricpressure.Figure68illustrateshowmuchthemanipulated
variableneedstochangetocompensatefortheseenvironmentalconditions.ThechartinFigure68
andtheexampleinFigure69serveasaguidelineforsettingtheO2MaxManVariableand
O2MinManVariableparameters.
Figure68:Theoretic
alChangeoftheManipulatedVariablewithChangesinAmbientTemperature
andPressure
WhentheO
2
ControlCurveiscommissioned,allburnerswillbeat(0,0)onthechart,wheretheXaxis
andYaxiscross.Asairtemperatureandbarometricpressurechangefromtheairtemperatureand
HOME

Table of Contents

Other manuals for Siemens LMV52.440B1

Related product manuals