UnsuccessfulVSDStandardization(continued)
6.  Monitorthespeedoftheblowermotorduringthestandardizationprocess.After
standardizationisactivated,therealtimespeedcanbereadusingthefollowingmenupath:
Params&Display>VSDModule>Speed>AbsoluteSpeed
 Duringstandardization,theabsolute speedshouldriseuptoapeakvalueandholdsteady
atthatvalueforafewseconds.Then,thevalueshoulddropbackdowntozero(ornear
zero).
 Thepeakvaluethatisseenshouldberecordedasthestandardizedspeed.Ifthisdoesn’t
happen,it’slikelythatthere’saproblemwiththeVSDorthespeedsensor.