Technical Instructions    LMV Series 
Document No. LV5-800
0 
Appendix A  Page 8  SCC Inc. 
Hot Standby on a Steam Boiler with an RWF50 or RWF55 (continued) 
 
LMV5 with an RWF5x for Hot Standby Contro
l Only 
 
Procedure 
1.  Wire the RWF5x to the LMV5 as shown in Figure 2. 
 
 
Figure 2:  LMV5 to RWF5x Hot Standby Only Wiring 
 
2.  Set the LMV5 for load controller operating mode “ExtLC X5-03” through the following 
menu path: 
 
Params & Display > LoadController > Configuration > LC_OptgMode =  
ExtLC X5-03 
 
3.  Set the following parameters in the RWF5x controller.  For more information, obtain 
Siemens Document No. U7866 for the RWF50 or Document No. U7867 for the RWF55 at 
www.scccombustion.com. 
 
ConF > Cntr > SPL = setpoint range lower limit 
ConF > Cntr > SPH = setpoint range upper limit 
OPr > SP1 = hot standby setpoint 
PArA > HYS1 = burner on for hot standby 
PArA > HYS3 = burner off for hot standby 
ConF > InP > InP1 > Sen1 = temperature sensor type