Technical Instructions    LMV Series 
Document No. LV5-800
0 
Appendix A  Page 16  SCC Inc. 
Low Fire Hold with an RWF55 (continued) 
 
Hot Water Boiler with an RWF55 with
 Analog Output 
1.  Set the following parameters in the LMV5: 
 
Params & Display > LoadController > Configuration > LC_OptgMode = ExtLC X62 
Params & Display > LoadController > Configuration > Ext Inp X62 U/I = 0..20 mA 
 
2.  Set the following parameters in the RWF55: 
 
ConF > Inp > Inp1 > SEn1 = type of RTD being used for temperature sensor 
ConF > Cntr > CtYP = 2 
ConF > AF > FnCt = 7 
ConF > AF > AL = temperature to enable low fire hold 
ConF > AF > HYSt = deadband around low fire hold temperature 
ConF > OutP > FnCt = 4 
ConF > OutP > SiGn = 0 
 
3.  Wire the LMV5 and RWF55 as shown in Figure 5: 
 
 
 
Figure 5:  Low Fire Hold via Analog Output on a Hot Water Boiler 
 
 
See page 19 for an example of the low fire hold operation.