LMV Series    Technical Instructions 
  Document No. LV5-80
00 
SCC Inc.  Page 21  Appendix A 
Pilot Valve Proving (continued) 
 
3.  The times for each of the
 four stages of valve proving need to be set.  To do so, use the 
following menu paths in the LMV5: 
 
Params & Display > BurnerControl > ValveProving > VP_EvacTme 
Params & Display > BurnerControl > ValveProving > VP_TmeAtmPress 
Params & Display > BurnerControl > ValveProving > VP_FillTme 
Params & Display > BurnerControl > ValveProving > VP_Tme_GasPress 
 
“VP_EvacTme” is the time that the downstream valve is energized in order to evacuate 
the chamber between the upstream and downstream valves (phase 80).  This is typically 
set to 3 seconds, but should not be set any less than the opening time of the valves. 
 
“VP_FillTme” is the time that the upstream valve is energized in order to pressurize the 
chamber between the upstream and downstream valves (phase 82).  This is typically set 
to 3 seconds, but should not be set any less than the opening time of the valves. 
 
“VP_TmeAtmPress” is the time that both the upstream and downstream valves are 
closed to test the leakage rate of the upstream valve (phase 81).  “VP_Tme_GasPress” is 
the time that both the upstream and downstream valves are closed to test the leakage 
rate of the downstream valve (phase 83).  Both of these times should be set to the same 
value.  These times can be calculated using the following equation: 
 
௧௦௧
 =
− 
௦௧
×  × 3600
௧
× 
 
 
t
test
 =  Time for setting parameters “VP
_TmeAtmPress” and “VP_Tme_GasPress” in 
seconds 
P
i
 =   Inlet gas pressure (pressure upstream of both valves) in PSIG 
P
set
 =   Gas pressure setting on pressure switch in PSIG (should be set for half of P
i
) 
P
atm
 =   Atmospheric pressure downstream of both valves in PSIA (typically 
14.7 PSI) 
  V =   Volume between the gas valves to be tested in ft
3
 
  Q
leak
 =  Allowable leakage rate in ft
3
/hr 
 
For Option 3, these times should be calculated independently for the pilot and main 
valves, and the larger of the calculated times should be used as the parameter setting. 
 
4.  Parameter “PreIgnitionTGas” should be set for its default of 2 seconds.  This parameter 
can be found at the following menu path in the LMV5: 
 
Params & Display > BurnerControl > Times > TimesStartup1 > PreIgnitionTGas