System
The term System” refers to registers defining the characteristics of the entire circuit board. System
registers report the same value independent of the slave address. Under BACnet structured view the
system points are grouped together.
Configuring Element and Channel Register for Service Types
The ViewPoint HD software enforces all element configurations to form a valid electrical system.
Configurations performed by remote systems may produce unexpected results if configurations are
internally inconsistent. The following tables document how to configure element and channel registers for
each service type. Every register should be explicitly written.
Red Text indicates Required Values, Purple Text indicates Suggested Defaults, if this data is not known.
Modbus Absolute Address/BACnet Object Assignments for Setting up Service Types
REGISTER
TEMPLATE
Service Type
2207
V_Input
2217
Description
2617
Channels
Volt Ref
CT Type
Range
Phase Shift
CT Multiplier
CT Sign
CH1
2220
2223
2224,2225
2224,2225
2221,2222
2226
CH2
2229
2232
2227,2228
2233,2234
2230,2231
2235
CH3
2238
2241
2236,2237
2242,2243
2239,2240
2244
Configurations
4 Wire 3 ɸ
(Wye)
Service Type
1
V_Input
1 or 2
Description
31 Char
Channels
Volt Ref
CT Type
Range
Phase
Shift
CT Multiplier
CT Sign
CH1
L1 N [1]
mV [1] or RōCoil [2]
Any > 0A
-3.0˚ to +3.0˚
Any > 0 [1]
0 or 1
CH2
L2 N [2]
mV [1] or RōCoil [2]
Any > 0A
-3.0˚ to +3.0˚
Any > 0 [1]
0 or 1
CH3
L3 N [3]
mV [1] or RōCoil [2]
Any > 0A
-3.0˚ to +3.0˚
Any > 0 [1]
0 or 1