Siemens Industry, Inc. 72
Appendix D— MD-xxHD Technical Specifications
Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three
Wire (Delta)
90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III.
Two voltage reference inputs (MD-48HD only)
12 (MD-12HD) or 48 (MD-48HD) channels, 0.525 VAC max, 333 mV CTs, 0-4,000
Amps depending on current transducer
150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to
4000A with RōCoil CTs.
True RMS using high-speed digital signal processing (DSP) with continuous
sampling
50-60 Hz (45 – 70 Hz measureable range) – measurement taken L1-N
From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max
Use of 12 volt auxiliary output requires 100 VAC minimum input voltage.
0.5A Fuse 200kA interrupt capacity
Unregulated 12VDC output, 200 mA, self-resetting fuse
1.8 kHz (MD-48HD), 3.6 HZ (MD-12HD)
Energy (kWh) values are recorded every 15 minutes for 63 days (downloadable
log)
Each record is time stamped.
Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import
(Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh,
Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered)
kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and
system total.
0.2% ANSI C12.20-2010 Class 0.2
Values reported in IEEE-754 single precision floating point format (32 bit)
Optional 4-line display, tri-color backlight (PhaseChek™)
Over/Under Voltage and Current (SPDT Relay - 30 Vdc)
MD-12HD – 4 inputs
MD-48HD – 2 inputs **
3.3V sourcing voltage (current limited) to customer dry contact pulse output
Maximum Pulse Rate 10 HZ (50 msec minimum transition time)
** Available Q4 2018
RS-485, Ethernet, & USB (for configuration only)
Modbus RTU or BACnet Master Slave Token Passing protocol (MS/TP)
Modbus (using SunSpec IEEE-754 single precision floating point model)
1200 meters with Data Range of 100K bits/second or less