18 MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3
Order No. 6SE6440- 2AD31
-8DA1
2AD32
-2DA1
2AD33
-0EA1
2AD33
-7EA1
2AD34
-5FA1
2AD35
-5FA1
2AD37
-5FA1
Fuse [A]
63 80 100 125 160 200 250
Recommended 3N
3822 3824 3830 3832 3836 3140 3144
for UL specified 3NE
1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0
Input Cable Min.
[mm
]
10.0 16.0 25.0 25.0 35.0 70.0 95.0
[awg]
8 6 3 3 2 2/0 3/0
Input Cable Max.
[mm
]
35.0 35.0 35.0 35.0 150.0 150.0 150.0
[awg]
2 2 2 2 300 300 300
Output Cable Min.
[mm
]
10.0 16.0 25.0 25.0 50.0 70.0 95.0
[awg]
8 6 3 3 1/0 2/0 3/0
Output Cable Max.
[mm
]
35.0 35.0 35.0 35.0 150.0 150.0 150.0
[awg]
2 2 2 2 300 300 300
Input voltage range 3 AC 380 V – 480 V. ± 10 % (Unfiltered)
Order No. 6SE6440- 2UD13
-7AA1
2UD15
-5AA1
2UD17
-5AA1
2UD21
-1AA1
2UD21
-5AA1
2UD22
-2BA1
2UD23
-0BA1
2UD24
-0BA1
2UD25
-5CA1
2UD27
-5CA1
Fuse [A]
10 10 10 10 10 16 16 20 20 32
Recommended 3N
3803 3803 3803 3803 3803 3805 3805 3807 3807 3812
for UL specified
*
*
******
**
Input Cable Min.
[mm
]
1.0 1.0 1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0
[awg]
18 18 18 18 18 16 16 14 14 12
Input Cable Max.
[mm
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 10.0
[awg]
14 14 14 14 14 10 10 10 8 8
Output Cable Min.
[mm
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 2.5 4.0
[awg]
18 18 18 18 18 18 18 18 14 12
Output Cable Max.
[mm
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 10.0
[awg]
14 14 14 14 14 10 10 10 8 8
Order No. 6SE6440- 2UD31
-1CA1
2UD31
-5DA1
2UD31
-8DA1
2UD32
-2DA1
2UD33
-0EA1
2UD33
-7EA1
2UD34
-5FA1
2UD35
-5FA1
2UD37
-5FA1
Fuse [A]
35 50 63 80 100 125 160 200 250
Recommended 3N
3814 3820 3822 3824 3830 3832 3836 3140 3144
for UL specified 3NE
* 1817-0 1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0
Input Cable Min.
[mm
]
6.0 10.0 10.0 16.0 25.0 25.0 35.0 70.0 95.0
[awg]
10 8 8 6 3 3 2 2/0 3/0
Input Cable Max.
[mm
]
10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0
[awg]
8 2 2 2 2 2 300 300 300
Output Cable Min.
[mm
]
6.0 10.0 10.0 16.0 25.0 25.0 35.0 70.0 95.0
[awg]
10 8 8 6 3 3 2 2/0 3/0
Output Cable Max.
[mm
]
10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0
[awg]
8 2 2 2 2 2 300 300 300
Input voltage range 3 AC 380 V – 480 V ± 10 % (Unfiltered)
Order No. 6SE6440- 2UD38-8FA1 2UD41-1FA1 2UD41-3GA1 2UD41-6GA1 2UD42-0GA1
Recommended Fuse
[A]
250 315 400 450 560
3NE
1227-0 1230-0 1332-0 1333-0 1435-0
Pipe cable shoe to
DIN 46235
[mm]
10 10 10 10 10
Input Cable Min.
[mm
]
1 x 95 or 2 x 35 1 x 150 or 2 x 50 1 x 185 or 2 x 70 1 x 240 or 2 x 70 2 x 95
[awg] or [kcmil]
1 x 4/0 or 2 x 2 1 x 300 or 2 x 1/0 1 x 400 or 2 x 2/0 1 x 500 or 2 x 2/0 2 x 4/0
Input Cable Max.
[mm
]
1 x 185 or 2 x 120 1 x 185 or 2 x 120 2 x 240 2 x 240 2 x 240
[awg] or [kcmil]
1 x 350 or 2 x 4/0 1 x 350 or 2 x 4/0 2 x 400 2 x 400 2 x 400
Output Cable Min.
[mm
]
1 x 95 or 2 x 35 1 x 150 or 2 x 50 1 x 185 or 2 x 70 1 x 240 or 2 x 70 2 x 95
[awg] or [kcmil]
1 x 4/0 or 2 x 2 1 x 300 or 2 x 1/0 1 x 400 or 2 x 2/0 1 x 500 or 2 x 2/0 2 x 4/0
Output Cable Max.
[mm
]
1 x 185 or 2 x 120 1 x 185 or 2 x 120 2 x 240 2 x 240 2 x 240
[awg] or [kcmil]
1 x 350 or 2 x 4/0 1 x 350 or 2 x 4/0 2 x 400 2 x 400 2 x 400