MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3 11
MM420 Specifications
Frame Size Dimensions Tightening torque for power connections
W x H x D
mm 73 x 173 x 149 Nm 1.1
inch 2.87 x 6.81 x 5.87 lbf.in 10
B W x H x D
mm 149 x 202 x 172 Nm 1.5
inch 5.87 x 7.95 x 6.77 lbf.in 13.3
C W x H x D
mm 185 x 245 x 195 Nm 2.25
inch 7.28 x 9.65 x 7.68 lbf.in 20
Input voltage range 1 AC 200 V – 240 V, ± 10 % (with built in Class A Filter)
Order No. 6SE6420- 2AB11-
2AA1
2AB12-
5AA1
2AB13-
7AA1
2AB15-
5AA1
2AB17-
5AA1
2AB21-
1BA1
2AB21-
5BA1
2AB22-
2BA1
2AB23-
0CA1
Fuse [A] 10 10 10 10 16 20 20 32 40
Recommended 3NA 3803 3803 3803 3803 3805 3807 3807 3812 3817
For UL specified * * * * * * * * *
Input Cable, min.
[mm
] 1.0 1.0 1.0 1.0 1.0 2.5 2.5 4.0 6.0
[awg] 18 18 18 18 18 16 16 12 10
Input Cable, max.
[mm
] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg] 14 14 14 14 14 10 10 10 8
Output Cable, min.
[mm
] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
[awg] 18 18 18 18 18 18 18 18 16
Output Cable, max.
[mm
] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg] 14 14 14 14 14 10 10 10 8
Input voltage range 1 AC 200 V – 240 V, ± 10 % (Unfiltered)
Order No. 6SE6420- 2UC11-
2AA1
2UC12-
5AA1
2UC13-
7AA1
2UC15-
5AA1
2UC17-
5AA1
2UC21-
1BA1
2UC21-
5BA1
2UC22-
2BA1
2UC23-
0CA1
Fuse [A] 10 10 10 10 16 20 20 32 40
Recommended 3NA 3803 3803 3803 3803 3805 3807 3807 3812 3817
For UL specified * * * * * * * * *
Input Cable, min.
[mm
] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 2.5
[awg] 18 18 18 18 18 18 18 18 14
Input Cable, max.
[mm
] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg] 14 14 14 14 14 10 10 10 8
Output Cable, min.
[mm
] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
[awg] 18 18 18 18 18 18 18 18 16
Output Cable, max.
[mm
] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg] 14 14 14 14 14 10 10 10 8
Input voltage range 3 AC 200 V – 240 V, ± 10 % (with built in Class A Filter)
Order No. 6SE6420- 2AC23
-0CA1
2AC24
-0CA1
2AC25
-5CA1
Fuse [A] 25 32 35
Recommended 3NA
3810 3812 3814
For UL specified * * *
Input Cable, min.
[mm
] 2.5 2.5 4.0
[awg] 14 14 12
Input Cable, max.
[mm
] 10.0 10.0 10.0
[awg] 8 8 8
Output Cable, min.
[mm
] 1.5 2.5 4.0
[awg] 16 14 12
Output Cable, max.
[mm
] 10.0 10.0 10.0
[awg] 8 8 8
*UL listed fuses, such as those stated in the warnings on page 2 are required for use in America.
*UL-gelistete Sicherungen, wie in den Warnhinweisen auf Seite 2 angegeben, sind für den Einsatz in Amerika vorgeschrieben.
*Des fusibles homologués UL, tels que ceux mentionnés dans les avertissements à la page 2 sont requis pour une utilisation en Amérique.
*I fusibili omologati UL, come quelli indicati nelle avvertenze a pagina 2, sono richiesti per l'utilizzo sul territorio americano.
*Para uso en Norteamérica se requieren fusibles conformes a UL, como los que figuran en las advertencias de la página 2.