MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3 15
Input voltage range 3 AC 380 V … 480 V, ± 10 % (Unfiltered)
Order No. 6SE6430- 2UD27
-5CA0
2UD31
-1CA0
2UD31
-5CA0
2UD31
-8DA0
2UD32
-2DA0
2UD33
-0DA0
Recommended Fuse
[A] 20 32 35 50 63 80
3NA 3807 3812 3814 3820 3822 3824
Fuses recomnended for
UL applications
[A] 50 63 80
3NE * * * 1817-0 1818-0 1820-0
Input Cable Min.
[mm
] 2,5 4,0 6,0 10,0 10,0 16,0
[AWG] 14 12 10 8 8 6
Input Cable Max.
[mm
] 10,0 10,0 10,0 35,0 35,0 35,0
[AWG] 8 8 8 2 2 2
Output Cable Min.
[mm
] 2,5 4,0 6,0 10,0 10,0 16,0
[AWG] 14 12 10 8 8 6
Output Cable Max.
[mm
] 10,0 10,0 10,0 35,0 35,0 35,0
[AWG] 8 8 8 2 2 2
Order No. 6SE6430- 2UD33
-7EA0
2UD34
-5EA0
2UD35
-5FA0
2UD37
-5FA0
2UD38
-8FA0
Recommended Fuse
[A] 100 125 160 200 250
3NA 3830 3832 3836 3140 3144
Fuses recomnended for
UL applications
[A] 100 125 160 200 250
3NE 1021-0 1022-0 1224-0 1225-0 1227-0
Input Cable Min.
[mm
] 25,0 25,0 35,0 70,0 70,0
[AWG] 3 3 2 2/0 2/0
Input Cable Max.
[mm
] 35,0 35,0 150,0 150,0 150,0
[AWG] 2 2 300 300 300
Output Cable Min.
[mm
] 25,0 25,0 35,0 70,0 95,0
[AWG] 3 3 2 2/0 4/0
Output Cable Max.
[mm
] 35,0 35,0 150,0 150,0 150,0
[AWG] 2 2 300 300 300
Input voltage range 3 AC 380 V … 480 V, ± 10 % (Unfiltered)
Order No. 6SE6430- 2UD41-1FA0 2UD41-3FA0 2UD41-6GA0 2UD42-0GA0 2UD42-5GA0
Recommended Fuse
[A] 250 315 400 450 560
3NE1227-0 3NE1230-0 3NE1332-0 3NE1333-0 3NE1435-0
Input Cable Min.
[mm
] 1 x 95 or 2 x 35 1 x 150 or 2 x 50 1 x 185 or 2 x 70 1 x 240 or 2 x 70 2 x 95
[AWG]
or [kcmil]
1 x 4/0 or 2 x 2 1 x 300 or 2 x 1/0 1 x 400 or 2 x 2/0 1 x 500 or 2 x 2/0 2 x 4/0
Input Cable Max.
[mm
] 1 x 185 or 2 x 120 1 x 185 or 2 x 120 2 x 240 2 x 240 2 x 240
[AWG]
or [kcmil]
1 x 350 or 2 x 4/0 1 x 350 or 2 x 4/0 2 x 400 2 x 400 2 x 400
Output Cable Min.
[mm
] 1 x 95 or 2 x 35 1 x 150 or 2 x 50 1 x 185 or 2 x 70 1 x 240 or 2 x 70 2 x 95
[AWG]
or [kcmil]
1 x 4/0 or 2 x 2 1 x 300 or 2 x 1/0 1 x 400 or 2 x 2/0 1 x 500 or 2 x 2/0 2 x 4/0
Output Cable Max.
[mm
] 1 x 185 or 2 x 120 1 x 185 or 2 x 120 2 x 240 2 x 240 2 x 240
[AWG]
or [kcmil]
1 x 350 or 2 x 4/0 1 x 350 or 2 x 4/0 2 x 400 2 x 400 2 x 400
Pipe cable shoe to
DIN 46235
[mm] 10 10 10 10 10
*UL listed fuses, such as those stated in the warnings on page 2 are required for use in America.
*UL-gelistete Sicherungen, wie in den Warnhinweisen auf Seite 2 angegeben, sind für den Einsatz in Amerika vorgeschrieben.
*Des fusibles homologués UL, tels que ceux mentionnés dans les avertissements à la page 2 sont requis pour une utilisation en Amérique.
*I fusibili omologati UL, come quelli indicati nelle avvertenze a pagina 2, sono richiesti per l'utilizzo sul territorio americano.
*Para uso en Norteamérica se requieren fusibles conformes a UL, como los que figuran en las advertencias de la página 2.