16 MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3
MM440 Specifications
Frame Size Dimensions
Tightening torque
for power connections
A
WxHxD
mm
73 u 173 u 149
Nm 1.1
inch
2.87 u 6.81 u 5.87
B
WxHxD
mm
149 u 202 u 172
Nm 1.5
inch
5.87 u 7.95 u 6.77
C
WxHxD
mm
185 u 245 u 195
Nm 2.25
inch
7.28 u 9.65 u 7.68
D
WxHxD
mm
275 u 520 u 245
Nm 10 (max.)
inch
10.82 u 20.47 u 9.65
E
WxHxD
mm
275 u 650 u 245
Nm 10 (max.)
inch
10.82 u 25.59 u 9.65
F
WxHxD
mm
350 u 850 Height with filter 1150
Nm 50
inch
13.78 u 33.46 u 12.60 Height with filter 45.28
FX
WxHxD
mm
326
u 1400 u 356
Nm 25
inch
12.80 u 55.12 u 12.83
GX
WxHxD
mm
326 u 1533 u 545
Nm 25
inch
12.80 u 60.35 u 21.46
Input voltage range 1 AC 200 V – 240 V, ± 10 % (with built in Class A Filter)
Order No. 6SE6440- 2AB11
-2AA1
2AB12
-5AA1
2AB13
-7AA1
2AB15
-5AA1
2AB17
-5AA1
2AB21
-1BA1
2AB21
-5BA1
2AB22
-2BA1
2AB23
-0CA1
Fuse [A]
10 10 10 16 16 20 20 32 40
Recommended 3N
3803 3803 3803 3805 3805 3807 3807 3812 3817
for UL specified
* * * * * * * * *
Input Cable Min.
[mm
]
1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0 6.0
[awg]
18 18 18 16 16 14 14 12 10
Input Cable Max.
[mm
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg]
14 14 14 14 14 10 10 10 8
Output Cable Min.
[mm
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
[awg]
18 18 18 18 18 18 18 18 16
Output Cable Max.
[mm
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg]
14 14 14 14 14 10 10 10 8
Input voltage range 1 AC 200 V – 240 V. ± 10 % (Unfiltered)
Order No. 6SE6440- 2UC11
-2AA1
2UC12
-5AA1
2UC13
-7AA1
2UC15
-5AA1
2UC17
-5AA1
2UC21
-1BA1
2UC21
-5BA1
2UC22
-2BA1
2UC23
-0CA1
Fuse [A]
10 10 10 16 16 20 20 32 40
Recommended 3N
3803 3803 3803 3805 3805 3807 3807 3812 3817
for UL specified
* * * * * * * * *
Input Cable Min.
[mm
]
1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0 6.0
[awg]
18 18 18 16 16 14 14 12 10
Input Cable Max.
[mm
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg]
14 14 14 14 14 10 10 10 8
Output Cable Min.
[mm
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
[awg]
18 18 18 18 18 18 18 18 16
Output Cable Max.
[mm
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg]
14 14 14 14 14 10 10 10 8
*UL listed fuses, such as those stated in the warnings on page 2 are required for use in America.
*UL-gelistete Sicherungen, wie in den Warnhinweisen auf Seite 2 angegeben, sind für den Einsatz in Amerika vorgeschrieben.
*Des fusibles homologués UL, tels que ceux mentionnés dans les avertissements à la page 2 sont requis pour une utilisation en Amérique.
*I fusibili omologati UL, come quelli indicati nelle avvertenze a pagina 2, sono richiesti per l'utilizzo sul territorio americano.
*Para uso en Norteamérica se requieren fusibles conformes a UL, como los que figuran en las advertencias de la página 2.