MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3 17
Input voltage range 3 AC 200 V – 240 V. ± 10 % (with built in Class A Filter)
Order No. 6SE6440- 2AC23
-0CA1
2AC24
-0CA1
2AC25
-5CA1
Fuse [A]
25 32 35
Recommended 3N
3810 3812 3814
for UL specified
* * *
Input Cable Min.
[mm
2
]
2.5 4.0 4.0
[awg]
14 12 12
Input Cable Max.
[mm
2
]
10.0 10.0 10.0
[awg]
8 8 8
Output Cable Min.
[mm
2
]
1.5 4.0 4.0
[awg]
16 12 12
Output Cable Max.
[mm
2
]
10.0 10.0 10.0
[awg]
8 8 8
Input voltage range 3 AC 200 V – 240 V. ± 10 % (Unfiltered)
Order No. 6SE6440- 2UC11
-2AA1
2UC12
-5AA1
2UC13
-7AA1
2UC15
-5AA1
2UC17
-5AA1
2UC21
-1BA1
2UC21
-5BA1
2UC22
-2BA1
2UC23
-0CA1
Fuse [A]
10 10 10 16 16 20 20 25 25
Recommended 3N
3803 3803 3803 3805 3805 3807 3807 3810 3810
for UL specified
* * * * * * * * *
Input Cable Min.
[mm
2
]
1.0 1.0 1.0 1.5 1.5 2.5 2.5 2.5 4.0
[awg]
18 18 18 16 16 14 14 14 12
Input Cable Max.
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg]
14 14 14 14 14 10 10 10 8
Output Cable Min.
[mm
2
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
[awg]
18 18 18 18 18 18 18 18 16
Output Cable Max.
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
[awg]
14 14 14 14 14 10 10 10 8
Order No. 6SE6440- 2UC24
-0CA1
2UC25
-5CA1
2UC27
-5DA1
2UC31
-1DA1
2UC31
-5DA1
2UC31
-8EA1
2UC32
-2EA1
2UC33
-0FA1
2UC33
-7FA1
2UC34
-5FA1
Fuse [A]
32 35 50 80 80 100 125 200 224/200 250
Recommended 3N
3812 3814 3820 3824 3824 3830 3832 3140 3142 3144
for UL specified 3NE
* * 1817-0 1820-0 1820-0 1021-0 1022-0 1225-0 1225-0 1227-0
Input Cable Min.
[mm
2
]
4.0 4.0 10.0 16.0 16.0 25.0 25.0 70.0 70.0 95.0
[awg]
12 12 8 6 6 3 3 2/0 2/0 3/0
Input Cable Max.
[mm
2
]
10.0 10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0
[awg]
8 8 2 2 2 2 2 300 300 300
Output Cable Min.
[mm
2
]
4.0 4.0 10.0 16.0 16.0 25.0 25.0 50.0 70.0 95.0
[awg]
12 12 8 6 6 3 3 1/0 2/0 3/0
Output Cable Max.
[mm
2
]
10.0 10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0
[awg]
8 8 2 2 2 2 2 300 300 300
Input voltage range 3 AC 380 V – 480 V. ± 10 % (with built in Class A Filter)
Order No. 6SE6440- 2AD22
-2BA1
2AD23
-0BA1
2AD24
-0BA1
2AD25
-5CA1
2AD27
-5CA1
2AD31
-1CA1
2AD31
-5DA1
Fuse [A]
16 16 20 20 32 35 50
Recommended 3N
3805 3805 3807 3807 3812 3814 3820
for UL specified 3NE
* * * * * * 1817-0
Input Cable Min.
[mm
2
]
1.5 1.5 2.5 2.5 4.0 6.0 10.0
[awg]
16 16 14 14 12 10 8
Input Cable Max.
[mm
2
]
6.0 6.0 6.0 10.0 10.0 10.0 35.0
[awg]
10 10 10 8 8 8 2
Output Cable Min.
[mm
2
]
1.0 1.0 1.0 2.5 4.0 6.0 10.0
[awg]
18 18 18 14 12 10 8
Output Cable Max.
[mm
2
]
6.0 6.0 6.0 10.0 10.0 10.0 35.0
[awg]
10 10 10 8 8 8 2