28 MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3
English Deutsch
P1120
0 - 650 s
Ramp-Up Time
Time taken for the motor to accelerate from
standstill up to maximum motor frequency
.
Rampenhochlaufzeit
Zeit für das Beschleunigen vom Stillstand bis
zur maximalen Motorfrequenz.
P1121
0 - 650 s
Ramp-Down Time
Time taken for motor to decelerate from maximum
motor frequency down to standstill
Rampenrücklaufzeit
Zeit zum Verzögern von höchster
Motorfrequenz bis zum Stillstand
P3900 End Quick Commissioning
0 = End Quick Commissioning without motor
calculation or factory reset.
1 = End Quick Commissioning with motor
calculation and factory reset
(Recommended).
2 = End Quick Commissioning with motor
calculation and with I/O reset.
3= End Quick Commissioning with motor
calculation but without I/O reset.
Ende Schnellinbetriebnahme
0 = Beendet die Schnellinbetriebnahme auf
Basis der aktuellen Einstellungen (ohne
Motorberechnung).
1 = Beendet die Schnellinbetriebnahme auf
Basis der Werkseinstellung (mit
Motorberechnung) (empfohlen).
2 = Beendet die Schnellinbetriebnahme auf der
Basis der aktuellen Einstellungen (mit
Motorberech-nung und E/A-Rücksetzung).
3= Beendet die Schnellinbetriebnahme auf der
Basis der aktuellen Einstellungen (mit
Motorberechnung, ohne E/A-Rücksetzung).