English 5. SYSTEM PARAMETERS
Parameter Function Range
[Default]
Description / Notes
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
32
P210
Transducer reading (%) 0.0 - 100.0
[-]
Read only. Value is a percentage of full scale of the selected input.
P211
0% setpoint 0.00-100.00
[0.00]
Value of P210 to be maintained for 0% setpoint.
P212
100% setpoint 0.00-100.00
[100.00]
Value of P210 to be maintained for 100% setpoint.
P220
PI frequency cut-off
0 - 1
[0]
0 = Normal operation
1 = Switch off inverter output at or below minimum frequency.
P700
P701
P702
P880
P910
Local/Remote mode 0 - 4
[0]
Sets the inverter for local control or remote control over the serial link:
0 = Local control
1 = Remote control (and setting of parameter values)
2 = Local control (but remote control of frequency)
3 = Remote control (but local control of frequency)
4 = Local control (but remote read and write access to
parameters and facility to reset trips)
Note: When operating the inverter via remote control (P910 = 1
or 3), the analogue input remains active when P006 = 1
and is added to the setpoint.
P918
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details
.
Access only possible with P099 = 1
P922
Software version 0.00 - 99.99
[-]
Contains the software version number and cannot be changed.
P923
Equipment system number 0 - 255
[0]
You can use this parameter to allocate a unique reference number to
the inverter. It has no operational effect.
P927
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details
.
P928
Access only possible with P099 = 1
P930
Most recent fault code 0 - 9999
[-]
The last recorded fault code (see section 6) is stored in this parameter.
This parameter can be cleared using the and buttons.
P931
Most recent warning type 0 - 9999
[-]
The last recorded warning is stored in this parameter until power is
removed from the inverter:
002 = Current limit active
003 = Voltage limit active
005 = Inverter over-temperature (Internal PTC)
P944
Reset to factory default settings 0 - 1
[0]
Set to ‘1’ and then press P to reset all parameters except P101 to the
factory default settings.
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details.
Access only possible with P099 = 1