Application planning
4
4.1 Secondary electrical conditions
4.1.1 Grounding concept
Components
The SINUMERIK 840D sl system consists of a number of individual components which have
been designed so that the system complies with the appropriate EMC and safety standards.
The individual system components are:
Numerical Control Unit (NCU):
Machine Control Panel MCP, Machine Push Button Panel MPP
Keyboard
Operator panels (operator panel front + TCU/PCU)
Distributor box and handheld unit
S7-300 I/O with IM 153 interface module
Grounding measures
The individual modules are attached to a metal cabinet panel. Insulating paints on the
mounting points must be removed.
It is permissible to have a cluster of operator components for ground connection/PA.
Example: The control panel on the swivel arm.
It is sufficient in this instance to connect the ground connections of, for example, the PCU,
TCU, and operator panel front using a cable and to route a shared grounding conductor to
the central ground connection in the control cabinet.
Additional references
Configuration Manual, EMC Guidelines