Accessories
7.1 Reactor and filter
PM250 Power Module
Hardware Installation Manual, 09/2012, A5E01003502B AD
59
Table 7- 2 Technical specifications of the output reactors (table 1 of 3)
Suitable for Power Module with rated power (HO) of
5.5 kW … 11 kW 15 kW 18.5 kW
Feature
FSC FSD FSD
MLFB of the output reactor 6SL3202-0AJ23-2CA0 6SE6400-3TC05-4DD0 6SE6400-3TC03-8DD0
MLFB of the suitable Power
Module
6SL3225-0BE25-5 . A0
6SL3225-0BE27-5 . A0
6SL3225-0BE31-1 . A0
6SL3225-0BE31-5 . A0 6SL3225-0BE31-8 . A0
Power loss at 50/60 Hz 60 W 200 W 200 W
Motor connection Screw terminals 6 mm² Flat connector for M6 cable
lug
Flat connector for M6 cable
lug
Connection to Power
Module
Cable, 350 mm length Flat connector for M6 cable
lug
Flat connector for M6 cable
lug
Degree of protection IP00 IP00 IP00
Overall dimensions
Width
Height
Depth
189 mm
334 mm
80 mm
225 mm
210 mm
150 mm
225 mm
210 mm
150 mm
Fixing dimensions
Width
Height
156 mm
232 mm
70 mm
176 mm
94 mm
176 mm
Fixing screw 4 × M5 4 × M6 4 × M6
Weight 9 kg 10.5 kg 16 kg
Possible as base
component
yes no no
Siemens Parts