Accessories
7.1 Reactor and filter
PM250 Power Module
60 Hardware Installation Manual, 09/2012, A5E01003502B AD
Table 7- 3 Technical specifications of the output reactors (table 2 of 3)
Suitable for Power Module with rated power (HO) of
22 kW 30 kW 37 kW
Feature
FSD FSE FSE
MLFB of the output reactor 6SE6400-3TC05-4DD0 6SE6400-3TC08-0ED0 6SE6400-3TC07-5ED0
MLFB of the suitable Power
Module
6SL3225-0BE32-2 . A0 6SL3225-0BE33-0 . A0 6SL3225-0BE33-7 . A0
Power loss at 50/60 Hz 200 W 170 W 270 W
Motor connection Flat connector for M6 cable
lug
Flat connector for M6 cable
lug
Flat connector for M6 cable
lug
Connection to Power
Module
Flat connector for M6 cable
lug
Flat connector for M6 cable
lug
Flat connector for M6 cable
lug
Degree of protection IP00 IP00 IP00
Overall dimensions
Width
Height
Depth
225 mm
210 mm
150 mm
225 mm
210 mm
150 mm
270 mm
248 mm
209 mm
Fixing dimensions
Width
Height
70 mm
176 mm
70 mm
176 mm
101 mm
200 mm
Fixing screw 4 × M6 4 × M6 4 × M8
Weight 10.5 kg 10.5 kg 25 kg
Possible as base
component
no no no