100 / 244   
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Detail pages: Inputs and outputs  01.02.2010 
Parameter  Range  Function 
Prio 03   Off / On / NULL  Value for priority 3: Not used. 
Prio 04  Fix Off  Value for priority 4 (always Off): Shut off for error. 
Prio 05  Off / On / NULL  Value for priority 5: Forced to a certain value, e.g. for frost 
protection. 
Prio 06  Off / On / NULL  Value for priority 6: For example, the minimum runtime for the 
element or overshoot time, e.g. dampers remain open until 
the fan is off. 
Prio 07  Off / On / NULL  Value for priority 7: Not used. 
Prio 08  Off / On / NULL  Value for priority 8: Manual intervention via HMI. 
Prio 09  Off / On / NULL  Value for priority 9: Special function to reset from priority 8 to 
auto mode. 
Prio 10 bis Prio 14  Off / On / NULL  Value for priority 10 through 14: Not used. 
Priority 15  Off / On / NULL  Value for priority 15: Normal plant operation. 
Priority 16  Off / On / NULL  Value for priority 16: Timeswitch catalogs. 
 
The lowest active priority controls the output. 
 
6.4  Multistate outputs 
6.4.1  General 
 
The details page for multistate outputs can be reached multiple ways, including: 
•  Main Index > Unit > Outputs > Analog outputs > Plant Element 
or 
•  Main Index > Unit > Element Control > Analog Element > Output Signal 
 
•  Main Index > Unit > Outputs > Digital outputs > Supply fan cmd 
or 
•  Main Index > Unit > Fan Control > Supply fan > Output signal 
 
 
Parameter  Range  Function 
Manual operation  –  Off 
–  Stage1 
–  Stage2 
–  Stage3 
–  NULL 
Manual operation on element (e.g. fan). Manual op-
eration is not automatically reset! An alarm can be 
triggered after a set period when the manual alarm 
function is enabled. 
NULL: Auto; The program controls the output. 
Present Value  –  NULL 
–  Off 
–  Stage1 
–  Stage2 
–  Stage3 
Present value for output. 
Access 
Example 
Parameter 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 100