73 / 244 
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Functions  01.02.2010 
Master Index > Unit > Temp control > Heat recovery > Frost 
Parameter  Range  Function 
Controller  0...100 [%]  Present value for the frost controlled. Go to con-
troller settings page. 
Setpoint  -64...64 [°C]  For temperature frost protection only! 
For one setpoint: Present setpoint for the frost 
controller. 
Fan stage 1 stpt  0...5000 [Pa]  For air-side frost protection only! 
Setpoint for the controller at fan stage 1. 
Fan stage 2/3 stpt  0...5000 [Pa]  For air-side frost protection only! 
Setpoint for the controller at fan stage 2 and 3. 
 
 
5.8  Heating / Heating 2 
5.8.1  General 
 
Heating / heating 2 is enabled and preconfigured in configuration 1, configuration 2 
and configuration I/Os. 
 
Main Index > Configuration > Configuration 1 
 
Parameter  Range  Function 
Heating / 
Heating 2 
–  No 
–  Yes 
–  Yes+Preheat 
–  No (additional) heating register. 
–  (Additional) heating register without preheating. 
–  (Additional) heating register with preheating. 
 
Main Index > Configuration > Configuration 2 
Parameter  Range  Function 
Htg frost protect / 
Heating 2 frost 
–  No 
–  sensor 
–  Sensor2Spv 
–  Detector 
–  Snsr+Dtctr 
–  2Spv+Dtctr 
–  No frost protection. 
–  Frost protection using a sensor. 
–  Frost protection using a sensor and 2 setpoints. 
–  Frost protection using a detector. 
–  Frost protection using a sensor and detector. 
–  Frost protection using a sensor, 2 setpoints and 
detector. 
Heating pump / 
Heating 2 pump 
–  No 
–  Yes 
–  Yes+Kick 
–  No heating register pump. 
–  Heating register pump without pump kick. 
–  Heating register pump with pump kick. 
Htg pump alarm / 
Heating 2 pump alm 
–  No 
–  Alarm 
–  Fdbk 
–  Both 
–  Pump without alarm or feedback. 
–  Pump with alarm. 
–  Pump with feedback. 
–  Pump with alarm and feedback. 
Heating 2 control  –  StandAlone 
–  InSequence 
–  Not integrated in sequence. 
–  Integrated in sequence. 
 
The hot ware registers can be operated with pump (pump kick, alarm, feedback) or 
without pump. Frost detection and controlled frost protection is integrated. The ad-
ditional heating register can be operated as a separate register with its own set-
point. The heating register is forced off if: 
–  Night unoccupied (temperaturstart) cool 
–  Summer night cooling 
–  Combicoil at summer (only heating, not heating2)  
 
A maximum of one of the two additional registers Heating 2 or El heating 2 can be 
integrated into the temperature control sequence. 
Parameter 
Prerequisite 
Enable heating group 
Configuration 
Function 
Note 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 73