77 / 244 
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Functions  01.02.2010 
Parameter  Range   
Outs air tmp X2  0.0...50.0 [°C]  Upper design temperature. 
Output signal Y1  0...100 [%]  Value for lower design temperature. 
Output signal Y2  0...100 [%]  Value for upper design temperature. 
Pre htg on time  0...600 [s]  Time to preheat lines and register. 
Min off time  0.0...1400.0 [min]  Minimum off time for the function after preheating is 
completed. 
 
 
5.9  Electrical heating / Electrical heating 2 
5.9.1  General 
 
Electrical heating / Electrical heating 2 are enabled and preconfigured in configura-
tion 1, configuration 2 and configuration I/Os. 
Main Index > Configuration > Configuration 1 
 
Parameter  Range  Function 
Electrical heating / 
El Heating 2 
–  No 
–  Analog 
–  No (additional) electric register. 
–  (Additional) electric register with analog con-
trol. 
  –  1Step  (Additional) single-stage electric heating register. 
  –  2Steps  (Additional) two-stage electric heating register. 
  –  3Steps  (Additional) three-stage electric heating register. 
 
Main Index > Configuration > Configuration 2 
Parameter  Range  Function 
El Htg alarm / 
El  heating 2 alarm 
–  No 
–  Alarm 
–  No alarm. 
–  With alarm. 
El heating 2 control   –  StandAlone 
–  InSequence 
–  Not integrated in sequence. 
–  Integrated in sequence. 
 
Both electric registers can be deployed with up to 3 stages (binary). An alarm is 
possible for each register. Register output is limited by fan out, which prevent the 
register from overheating. The additional electric heating register can be operated 
as a separate register with its own setpoint.  
The electrical heating register is forced off if: 
–  Night unoccupied (temperaturstart) cool 
–  Summer night cooling 
 
A maximum of one of the two additional registers Heating 2 or El heating 2 can be 
integrated into the temperature control sequence. 
The stages are controlled as follows for electric heating registers: 
  DO1  DO2 
Off 
0  0 
Stage1 
1  0 
Stage2 
0  1 
Stage3 
1  1 
 
 
 
Prerequisite 
Enable electric register 
Configuration 
Function 
Note 
Stage control 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 77