230 / 244   
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Appendices  01.02.2010 
20  Appendices 
20.1  Point tables 
 
As a matter of principle, we recommend the following configuration procedure: 
1.  During configuration (Configuration 1 and Configuration 2) all required I/Os in 
the table must be executed using the following sample. 
2.  Clean up the tables prior to starting I/O configuration. 
3.  Conduct I/O configuration per the table. 
 
This ensures that 
–  The plant on the basis controller and the planned extension modules fit. 
–  It is evident at all times which terminals used for the required inputs and outputs. 
 
Hardware assignment for the basis controller POL683x 
IO  Function  IO type  Connection   Comments 
Digital outputs 
 
DO1    Digital  T6 (Q13,Q14)   
DO2    Digital  T6 (Q23,Q24)   
DO3    Digital  T6 (Q33,Q34)   
DO4    Digital  T6 (Q43,Q44)   
DO5    Digital  T7 (Q53,Q54)   
DO6    Digital  T7 (Q63,Q64)   
Analog outputs 
 
AO1    0...10 V DC  T3 (Y1,M)   
AO2    0...10 V DC  T3 (Y2,M)   
Binary inputs 
     
DI1    Digital  T4 (D1,M)   
DI2    Digital  T4 (D2,M)   
DI3    Digital  T4 (D3,M)   
DI4    Digital  T4 (D4,M)   
DI5    Digital  T4 (D5,M)   
Universal inputs 
 
X
1
      T2 (X1,M)   
X2      T2 (X2,M)   
Universal inputs / outputs       
X3      T2 (X3,M)   
X4      T2 (X4,M)   
X5      T2 (X5,M)   
X6      T2 (X6,M)   
X7      T2 (X7,M)   
X8         
 
–  Universals I/Os X1 and X2 can be configured exclusively as inputs (digital, 
Ni1000, Pt1000, NTC10K, 0-10V DC). 
–  Universals I/Os X3 – X8 can be configured as inputs (digital, Ni1000, Pt1000, 
NTC10K, 0-10V DC) or outputs 0-10V DC. 
 
Basis controller 
Notes 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 230