8  Detail pages: Time switch program 
8.1  General 
 
This section describes the functions and entries for time switch catalogs and cal-
endars. 
Possible entries vary depending on the configuration. It is set in Configuration 1: 
Main Index > Configuration > Configuration 1 > TSP function 
Main Index > Configuration > Configuration 1 > TSP steps 
The time switch catalog/calendar available in auxiliary has the set entries Off and 
On: 
Main Index > Configuration > Configuration 2 > Aux TSP output 
If no element is active at a higher priority (e.g. Manual Operation <> Auto), the 
plant can be switched to off or any stage using a time switch catalog (for analog 
controlled fans to the given stage setpoint). A maximum of 6 switching entries are 
possible per week. 
The calendar Fix Off (in operating mode only) override the calendar exception and 
this in turn overrides the normal time switch catalog. Up to 10 periods or exception 
days can be defined for each calendar. 
TSP function=Steps+Tmp: The time switch program determines both fan stage 
setpoint as well as the temperature setpoint (Comfort/Economy). 
 
 
8.2  Week scheduler 
 
Main Index > Unit > Main overview > Time switch program > Schedule 
Parameter  Range  Function 
Present value  ---  Resulting switching command from the sched-
uler. 
Monday  −  Passive 
−  Active 
Display is enabled of the present day is Monday. 
The last entry for the day applies to 23:59. Go to 
the daily switching plan for Monday. 
Copy schedule   
 
−  Monday to  
−  Tu to Fr 
Copies entries for the time switch program from 
Monday to Tuesday through Friday: 
−  Passive position (copy disabled). 
−  Copy starts. Returns to display. 
Tuesday    Similar to Monday. 
...    ... 
Sunday    Similar to Monday. 
Exception    Displays the enabled command, when the pre-
sent day is an exception day. Go to daily switch-
ing plan for exception days. 
Calendar in auxiliary 
Function 
Note 
Parameter 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB