5.11.7  Humidifier pump kick 
 
Pump kick is enabled. 
Main Index > Configuration > Configuration 2 > Humidifier pump = Yes+Kick 
The pump is switched on for a short period for longer idle periods. This prevents 
lock up. 
Main Index > Unit > Humidity control > Humidification > Pump 
Parameter  Range  Function 
Kick date / time  Mo 00:00...So 23:29  Weekday and time for pump kick. Sets the weekday 
(Mon...Sun) and time to run the pump kick.  
Examples: 
Mon *:*  Each Monday at midnight. 
Sat 07:*  Each Saturday at 7:00 am. 
* *:*  Time is not relevant; the kick interval applies 
accordingly. 
Kick interval  0.0...36000.0 [h]  Idle time for pump kick. Set the idle time after which a 
pump kick is run. Examples: 
168  After 168 hours. 
123.4  After 123 hours and 24 minutes. 
0  Idle time is not relevant; kick date/time applies 
accordingly. 
Kick on time  0.0...36000 [s]  Set the period for the pump kick. 
Examples: 
10  Period = 10 seconds. 
0  Period = 1 controller cycle (ca. 150 ms). 
 
Kick date/time = * *:* and kick interval = 0 --->  
No pump kick is run. 
 
 
5.11.8  Fan compensation 
 
Main Index > Configuration > Configuration 1 > Room hum sensor = Yes 
Main Index > Configuration > Configuration 2 > Fan comp humidity = Yes 
 
Main Index > Configuration > Configuration 2 
Parameter  Range  Function 
Fan comp humidity  –  No 
–  Yes 
Room-temperature dependent fan compensation. 
 
The controller output reduces or increases the fan setpoint relating to the maximum 
allowable fan compensation (See as well Fan compensation). 
Fan setpoints are increased or decreased, if: 
–  KP > 0: Room humidity < setpoint. 
–  KP < 0: Room humidity > setpoint 
 
 
 
 
Prerequisite 
Function 
Parameter 
Note 
Prerequisite 
Enable 
Function 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 89