SPECIAL FEATURES
VARI-AMP
TM
RANGE AND CURRENT RATINGS AVAILABLE
±10% ±8 3/4% ±7 1/2% ±6 1/4% ±5%
10-02.5-050.0 200 220 240 270 320
10-02.5-075.0 300 330 360 405 480
10-02.5-100.0 400 440 480 540 640
10-02.5-167.0 668 668 668 668 668
10-02.5-250.0 1000 1000 1000 1000 1000
10-02.5-333.0 1332 1332 1332 1332 1332
11-02.5-416.3 1665 1665 1665 1665 1665
10-05.0-050.0 100 110 120 135 160
10-05.0-100.0 200 220 240 270 320
10-05.0-167.0 334 367 401 451 534
10-05.0-250.0 500 550 600 668 668
10-05.0-333.0 668 668 668 668 668
11-05.0-416.3 835 835 835 835 835
10-07.6-038.1 50 55 60 68 80
10-07.6-057.2 75 83 90 102 120
10-07.6-076.2 100 110 120 135 160
10-07.6-114.3 150 165 180 203 240
10-07.6-167.0 219 241 263 296 351
10-07.6-250.0* 328/347 361/381 394/416 443/468 525/555
10-07.6-333.0* 437/463 481/509 524/556 590/625 668/668
10-07.6-416.3* 546/578 601/636 656/668 668/668 668/668
10-07.6-500.0 656 668 668 668 668
10-07.6-667.0 875 875 875 875 875
11-07.6-889.0 1167 1167 1167 1167 1167
10-13.8-069.0 50 55 60 68 80
10-13.8-138.0 100 110 120 135 160
10-13.8-207.0 150 165 180 203 240
10-13.8-276.0 200 220 240 270 320
10-14.4-072.0 50 55 60 68 80
10-14.4-144.0 100 110 120 135 160
10-14.4-288.0 200 220 240 270 320
10-14.4-333.0 231 254 277 312 370
10-14.4-432.0 300 330 360 405 480
10-14.4-576.0 400 440 480 540 640
11-14.4-720.0 500 550 600 668 668
10-14.4-833.0 578 636 668 668 668
10-19.9-100.0 50 55 60 68 80
10-19.9-200.0 100 110 120 135 160
10-19.9-333.0 167 184 201 226 268
10-19.9-400.0 200 220 240 270 320
10-19.9-667.0 335 368 402 452 536
11-19.9-833.0 418 459 502 565 668
Units with catalog number starting with:
10 are self cooled
11 are forced-air cooled
Regulators can be modified at factory for 50
Hz operation with appropriate de-rating of
voltage.
*Capable of carrying current corresponding
to rated kVA when operated at 7200/12470
volts ground wye.
OPERATION AT LESS
THAN
RATED VOLTAGE
JFR regulators may be operated at less
than the voltage for which they were de-
signed. All system voltages for which
control system taps have been provided
are shown on the nameplate. When this
is to be accomplished it may be neces-
sary to reconnect particular leads at the
upper 19-pin terminal block as illustrated
on page 5. When operating the regulator
at reduced voltage it must be noted that
the regulator carries a maximum current
rating which rules regardless of the
voltage (see table at right). It may
therefore be necessary to operate the
regulator at less than its nameplate kVA
rating.