Hardware Features
Compact Series Specifications
29 |
100
Technical Reference Manual
145-172
Restricted
2018-09-25
Processor, Battery, and Memory
Processor and Clock Speed PXC-16 and PXC-24: Freescale MPC852T, 100 MHz
PXC-36: Freescale MPC885, 133 MHz
Memory PXC-16 and PXC-24: 24 MB (16 MB SDRAM, 8 MB Flash ROM)
PXC-16/24 “F” and “F32”: 40 MB (32 MB SDRAM, 8 MB Flash ROM)
PXC-36: 80 MB (64 MB SDRAM, 16 MB Flash ROM)
NOTE:
See the Configuration and Sizing Guidelines document for supported memory size.
New PXC models will now support high speed 480 Mbps communication (PXC-36 only).
Serial EEPROM 4 KB
Battery backup of Synchronous Dynamic
(SD) RAM (field replaceable)
Non-
rooftop Models
AA (LR6) 1.5 Volt Alkaline (non-rechargeable)
PXC-16 and PXC-24: 180 days (accumulated)
PXC-16 and PXC-24 F and F32: 110 days (accumulated)
PXC-36: 60 days (accumulated)
Rooftop (Extended
Temperature) Models
AA (LR6) 3.6 Volt Lithium (non-rechargeable): 90 days (accumulated)
32MB SDRAM Rooftop (lithium): 200 days
16MB SDRAM Rooftop (lithium): 330 days
Battery backup of Real Time Clock
Non-
rooftop Models
10 years (32°F to 122°F (0°C to 50°C))
Coin cell (BR2032) 3 Volt lithium
Rooftop (Extended Temperature) Models
18 months (-40°F to 158°F (-40°C to 70°C))
Coin cell (BR2032) 3 Volt lithium
These are typical accumulated times while power is off.
Communication
BACnet/IP or Ethernet TCP/IP (P2)
Automation Level Network (ALN) or
BACnet/IP or Ethernet TCP/IP (P2) Floor
Level Network (FLN)
10Base-T or 100Base-TX compliant
10 Mbps or 100 Mbps (autoswitching) over Ethernet cable, RJ-45 jack, shielded, 328 ft (100
m) max. from the field panel to the nearest active hub, router, or signal repeater. Up to 100
nodes per BACnet/IP or Ethernet TCP/IP (P2) ALN or FLN.
10Base-
T Connection Requirements
UTP/STP Category 3 or 5 or better cable
100Base-TX Connection Require
ments
UTP/STP Category 5 or better cable
Supports CSMA/CD protocol, compatible with IEEE 802.xx compliant devices.
PXC-36 supports Auto-MDIX
BACnet MS/TP Automation Level Network
(ALN)
9600 bps to 115.2 Kbps, up to 10 nodes per MS/TP ALN
RS-485 Automation Level Network (ALN)
1200 bps to 115.2 Kbps over 24-gauge, low capacitance shielded twisted pair cable, 4000 ft
(1220 m) max. @ 57.6 Kbps or less, 3280 ft (1 km) max. @ 115.2 Kbps. Up to 100 nodes per
RS-485 ALN.
Human-Machine Interface (HMI)
Three wire, full-duplex, asynchronous serial RS-232 compliant, 1200 bps to 115.2 Kbps, 8-N-
1, no hardware flow control (Xon/Xoff supported). RJ-45 jack, 50 ft (16 m) max. cable length.
Supports dial-in modem.
Factory-
set HMI Communication Speed
PXC-16 and PXC-24: 9600 bps
PXC-36: 115.2 Kbps

Table of Contents

Other manuals for Siemens PXC Modular Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens PXC Modular Series and is the answer not in the manual?

Siemens PXC Modular Series Specifications

General IconGeneral
BrandSiemens
ModelPXC Modular Series
CategoryControl Unit
LanguageEnglish

Related product manuals