Unitary Equipment Controller
Technical Reference Manual
Ambient operating environment
Operate in a dry location, which is protected from exposure to salt spray or other corrosive
elements. Exposure to flammable or explosive vapors must be prevented.
Ambient operating temperature 32°F to 122°F (0°C to 50°C)
Relative Humidity 5 to 95% rh non-condensing
Shipping and storage environment -40°F to 185°F (-40°C to 85°C)
Mounting Surface Direct equipment mount, building wall, or structural member
Must be installed inside a metal enclosure rated at IP20 minimum
Vibration Compliance to IEC 60721, Class 2M2 and 3M2
Protection to EN60529 IP 20
UL
UL916 PAZX (all models)
UL916 PAZX7 (all models)
Agency Compliance
FCC Compliance CFR47 Part 15, Subpart B, Class B
Australian EMC Framework
European EMC Directive (CE)
European Low Voltage Directive (LVD)BACnet Testing Laboratories (BTL) Certified, Firmware
Revision 3.0 and later
Electrical Disturbance Testing
Dips and Interrupts per EN 61000-4-11
Electrical Fast Transients (EFT)
per EN 61000-4-4
1 kV signal, 2 kV AC power
Electrical Surge Immunity
per EN 61000-4-5
AC power: 2 kV common mode, 1 kV differential mode
Electrostatic Discharge (ESD) per EN 61000-4-2, 6 kV contact, 8 kV air discharge
RF Conducted Immunity per EN 61000-4-6 @ 10V
RF Radiated Immunity per EN 61000-4-3 @ 10V/m