Technical Instructions  Q-Series Outdoor Air and Critical Environment  
Document Number 155-755  Relative Humidity and Relative Humidity & Temperature Sensors 
February 28, 2013 
Page 6   Siemens Industry, Inc. 
 
Specifications 
Power Supply 
Operating voltage  24 Vac 
+ 20% or 13.5 to 35 Vdc 
Frequency  50/60 Hz at 24 Vac 
Power consumption 
< 1 VA 
Humidity element 
Operating range  0 to 100% rh 
Measurement range  0 to 95% rh 
Accuracy at room temperature (73°F [20°C]) 
+ 2% rh, 0 to 95% rh 
Time constant  Approx. 20 s in moving air 
Output signal, linear (terminal U1)  0 to 10 Vdc = 0 to 100% rh 
  Max. 
+ 1 mA 
Operating temperature  -40°F to 158°F (-40°C to 70°C) 
Temperature effect  < 0.1% per degree Celsius 
Sensing element  Capacitive humidity sensing element 
Output signal (rh only units)  4 to 20 mA or 0 to 10 Vdc, 0 to 100% 
  linear, proportional 
Output signal (rh/T units)  4 to 20 mA or 0 to 10 Vdc, 0 to 100% 
  linear, proportional 
Polarity protection  Yes 
Temperature element 
(for combination rh/T 
units only) 
Operating temperature, jumper selectable  32°F to 122°F (0°C to 50°C) or 
      -31°F to 95°F (-35°C to 35°C), 
      -40°F to 158°F (-40°C to 70°C) 
Time constant @ 32°F to 122°F  Approximately 20 s in moving air 
(0°C to 50°C) and 10 to 80% rh 
Accuracy 
  @ 32°F to 122°F (0°C to 50°C) 
+ 1.8°F (+ 1°C) 
  @ -31°F to 95°F (-35°C to 35°C) 
+ 1.4°F (+ 0.8°C) 
  @ 32°F to 158°F (0°C to 70°C) 
+ 1.8°F (+ 1°C) 
Output signal  4 to 20 mA or 0 to 10 Vdc, 0 to 100% 
  linear, proportional 
Calibration adjustments  None 
General 
Installation  18 AWG cable length shared in 
      conduit with other sensor wiring. 
      750 ft (229 m) maximum 
Connections Screw terminals 
Dimensions 
  Outdoor air probe  6" OD × 3.3" L (15 mm × 84 mm) 
  Outdoor air housing  3.1" L × 2.3" W × 1.5" D 
      (80 mm × 60 mm × 40 mm) 
  Shield (mounted)  3.43" H × 3.5" W × 4.1" D  
      (87 mm × 89 mm × 104 mm) 
Voltage requirement  13.5 to 35 Vdc 
Material type  Polycarbonate plastic 
Protection class rating  IP 65 (NEMA 4) 
Agency certification 
 Conforms to  EMC Directive 89/336/EEC 
UL Listing  UL873 XAPX 
cUL Listing  Canadian Standard C22.2 No. 24-93 
 Conforms to Australian EMC  Radio Communication Act 1992 
Framework Radio Interference Emission  AS/NZS 3548 
Standard