Siemens RDE100.1DHW Room thermostat with Auto Timer, independent DHW CB1N1423en_01
Building Technologies 2013-03-15
Maintenance notes
The thermostats are maintenance-free.
Disposal
In terms of disposal, the room thermostats are classified as electronic scrap con-
forming to the European Directive 2011/65/EU (WEEE) and must not be disposed
of as unsorted domestic waste. The relevant national legal regulations must be
complied with and the units must be disposed of via the appropriate channels.
Local and currently valid legislation must be observed.
Technical data
Operating voltage
RDE100.1DHW
DC 3 V (2 x 1.5 V alkaline batteries AAA)
For battery life (RDE100.1DHW), see below (alkaline batteries type AAA).
Battery life calculation is based on the touchpad scanning rate during idle time
(assuming a user presses 4 touchkeys per day):
Scanning rate 0.25 s
Scanning rate 0.50 s
Scanning rate 1.00 s
Scanning rate 1.50 s
193 days battery life
273 days battery life
345 days battery life
378 days battery life
Control input Q11-Nx (Com)
Control input Q21-Nx (Com)
(AC 24...230 V) max. 5(2) A min. 8 mA
(AC 24...230 V) max. 5(2) A min. 8 mA
Heating valve or wall-hung boiler
Control output Q12-Nx (NC contact)
Control output Q14-Nx (NO contact)
(AC 24…230 V) max. 5(2) A min. 8 mA
(AC 24...230 V) max. 5(2) A min. 8 mA
DHW heating equipment
Control output Q22-Nx (NC contact)
Control output Q24-Nx (NO contact)
(AC 24…230 V) max. 5(2) A min. 8 mA
(AC 24...230 V) max. 5(2) A min. 8 mA
Switching differential SD
Comfort mode
Economy mode
Holiday mode
1 K
20 °C (5...35 °C)
16 °C (5...35 °C)
12 °C (5...35 °C) (Standalone)
Built-in room temperature sensor
Setpoint setting range
Accuracy at 25 °C
Temperature calibration range
5…35 °C (Comfort/Economy mode)
< ±0.5 K
±3.0 K
Resolution of settings and displays
Setpoints
Temperature value displays
0.5 °C
0.5 °C
Operation
Climatic conditions
Temperature
Humidity
As per IEC 60721-3-3
Class 3K5
0…50 °C
<95% r.h.
Power supply
Control inputs
Control outputs
Function data
Environmental
conditions