44 / 66
Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en
Building Technologies Functions 14 Dec 2011
4.11 Auto timer (RDG100T, RDG100T/H only)
The thermostat provides an Auto Timer mode with 8 programmable timers.
Each timer can be assigned to one or several days. In this mode, the thermostat
automatically changes over between Comfort and Economy mode according to the
preprogrammed timers.
Button
= bottom, button = top (see operating instructions B3181.4).
1. Press the program mode button to enter the programming mode menu.
2. Press button
(OK) to enter the setting mode for the time of day.
The time digits start blinking.
3. Turn the rotary knob clock- or counterclockwise to set the time of day.
If the current time of day is in 24-hour format and you wish to change it to 12-hour
format, turn the knob clockwise passed 23:59 or counterclockwise passed 00:00.
If the current time of day is in 12-hour format and you wish to change it to 24-hour
format, turn the knob clockwise passed 12:00 pm or counterclockwise passed
12:00 am.
4. Confirm the time of day by pressing the right button
The weekday indicator starts blinking.
5. Turn the rotary knob clock- or counterclockwise to set the current weekday.
6. Confirm the current weekday by pressing button
(OK).
7. Press the program mode button
(Esc) to leave the program mode.
Time and weekday are always visible on the display, even when auto timer is OFF
(P02 = 3 or 4 on RDG100T/H and RDG100T with SW V7.2 and higher / device
index E).
After a power failure, the time of day will blink to indicate power was lost.
However the auto timer will continue to run with the time before the power loss
occurred. Enter the setting mode to adjust the time of day if needed.
Buttons of the
RDG100T/H
Setting the time of day
and the weekday
12-hour and 24-hour
format
Note
Power failure