Functions
Communication objects
4
A6V11545892_en--_c
133 | 180
Obj
Object name
Function
Type/
length
Flags
Obj
Object name
Function
Type/
length
Flags
93
Room temp:
Current cooling
setpoint (receive)
Temperature
9.001
2 bytes
CWU
99
DC fan speed:
Maximum speed
cooling
0...100 %
5.001
1 byte
CWU
Communication object adjusts the current cooling setpoint
received by the thermostat from bus (see Setting and adjusting
setpoints [ 38]).
The range is 5...40 °C.
S-Mode object needs to be enabled by setting Room temp:
Current setpoint to as group object in ETS.
DC fan speed for maximum cooling output received via bus.
100
Built-in room air
quality value
Air quality
9.008
2 bytes
CRT
The value of the room air quality value (CO
2
) measured via built-in
sensor or external sensor is available on bus. (Manager)
94
Room operating
mode: Status
(receive)
Comfort
Economy
Protection
20.102
1 byte
CWU
101
External room air
quality value
Air quality
9.008|
2 bytes
CWU
Actual room operating mode received by the thermostat
(Manager) from bus (considering time switch, user selection,
window contact, etc.) This state information is available via one 8-
bit enumeration.
The thermostat (Subordinate) receives and works with the room
air quality value from an external sensor.
95
ChangeOverWater
status (send)
Heating: 1
Cooling: 0
1.100
1 bit
CRT
102
DC damper
demand
0…100 %
5.001
1 byte
CRT
Sends the water changeover information.
Indicates the control status of DC damper.
96
ChangeOverWater
status (receive)
Heating: 1
Cooling: 0
1.100
1 bit
CWU
103
On/Off damper
demand
On
Off
1.001
1 bit
CRT
Water changeover information received via bus.
Indicates the control status of On/Off damper.
97
Manual fan
command value
(send)
0...100 %
5.001
1 byte
CRT
Sends the manual fan command value.
98
DC fan speed:
Maximum speed
heating
0...100 %
5.001
1 byte
CWU
DC fan speed for maximum heating output received via bus.

Table of Contents

Other manuals for Siemens RDG2 KN Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDG2 KN Series and is the answer not in the manual?

Siemens RDG2 KN Series Specifications

General IconGeneral
BrandSiemens
ModelRDG2 KN Series
CategoryThermostat
LanguageEnglish

Related product manuals