42 EMC and Environmental Type Tests
Environmental Type Tests
Test Description Test Levels Severity Levels
Cold Temperature Test Ad -40 °C (-40 °F), 16 HoursIEC 60068-2-1
Cold Storage Test Ab -40 °C (-40 °F), 16 Hours
Dry Heat Test Bd 85 °C (185 °F), 16 HoursIEC 60068-2-2
Dry Heat Storage Test Bd 85 °C (185 °F), 16 Hours
IEC 60068-2-30 Humidity (Damp
Heat, Cyclic)
Test Dd 95% (Non-Condensing),
55 °C (131 °F), 6 Cycles
IEC 60068-2-14 Change of Temperature Test Nb 5 Cycles @ -40 to 85
°C (-40 to 185 °F)
IEC 60068-2-78 Humidity (Damp
Heat, Cyclic)
Test Cab 10 Days @ 55 °C
(131 °F), 6 Cycles
IEC 60255-21-1 Vibration 2 g @ 10 to 150 Hz Class 2
IEC 60255-21-2 Shock 30 g @ 11 ms Class 2
IEC 60255-21-2 Bump 10 g @ 16 ms Class 1
IEC 60255-21-3 Seismic Method A Class 2
IEC 60529 Ingress Protection IP4x