Connecting High AC/DC Power 11
Equipment must be installed according to applicable local wiring codes and standards.
CONTENTS
Section2.6.1, “Connecting High AC/DC Power”
Section2.6.2, “Connecting Low DC Power”
Section2.6.1
Connecting High AC/DC Power
To connect a high AC/DC power supply to the device, do the following:
DANGER!
Electrocution hazard – risk of death, serious personal injury and/or damage to the device. Make sure
the supplied cover is always installed over high voltage screw-type terminal blocks.
CAUTION!
Electrical hazard – risk of damage to equipment. Do not connect AC power cables to a 12, 24 or 48 VDC
power supply terminal block. Damage to the power supply may occur.
NOTE
The screw-type terminal block is installed using Phillips screws and compression plates, allowing either
bare wire connections or crimped terminal lugs. Use #6 size ring lugs for secure, reliable connections.
1. Connect the power supply terminal block to the device.
1
2
3
4
Figure5:AC Terminal Block Wiring – Pluggable Terminal Block for HIP Power Supplies
1.3-Position Terminal Block 2.Positive/Live (+/L) Terminal 3.Ground Terminal 4.Negative/Neutral (-/N) Terminal