Chapter 6
Certification
RUGGEDCOM RX1510
Installation Guide
40 Other Approvals
Section6.1.7
Other Approvals
This device meets the requirements of the following additional standards:
• IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Requirements
Section6.2
EMC and Environmental Type Tests
The RUGGEDCOM RX1510 has passed the following Electromagnetic Compatibility (EMC) and environmental tests.
EMC Type Test for IEC 61850-3
Test Description Test Levels
Severity
Levels
Enclosure Contact ± 8 kVIEC 61000-4-2 ESD
Enclosure Air ± 15 kV
4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 V/m
Signal ports ± 4 kV @ 2.5 kHz
Note
a
DC Power Ports
AC Power Ports
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
± 4 kV 4
Signal ports ± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
DC Power Ports ± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC 61000-4-5 Surge
AC Power Ports ± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal ports
DC Power Ports
AC Power Ports
IEC 61000-4-6 Induced (Conducted) RFI
Earth ground ports
10 V 3
IEC 61000-4-8 Magnetic Field Enclosure Ports 100 A/m, continuous
1000 A/m for 1 s
Note
a