RUGGEDCOM RX1510
Installation Guide
Chapter 6
Certification
EMC and Environmental Type Tests 41
Test Description Test Levels
Severity
Levels
1000 A/m for 1 s 5
IEC 61000-4-11 Voltage Dips and Interrupts AC Power Ports 30% for 1 period
60% for 50 periods
Signal ports
DC Power Ports
IEC 61000-4-12 Damped Oscillatory
AC Power Ports
2.5 kV common, 1 kV
differential mode @1 MHz
3
Signal portsIEC 61000-4-16 Mains Frequency Voltage
DC Power Ports
30 V Continuous
300 V for 1 s
4
IEC 61000-4-17 Ripple on DC Power Supply DC Power Ports 10% 3
IEC 61000-4-29 Voltage Dips and Interrupts DC Power Ports 30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal ports 2 kV (Failsafe Relay output)
DC Power Ports 1.5 kV
Dielectric Strength
AC Power Ports 2 kV
Signal ports 5 kV (Failsafe Relay output)
DC Power Ports
IEC 60255-5
HV Impulse
AC Power Ports
5 kV
a
Siemens-specified severity levels
EMC Immunity Type Tests for IEEE 1613
NOTE
The RUGGEDCOM RX1510 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires
error-free and interrupted communications.
Description Test Levels
Signal ports 5 kV (Failsafe Relay Output)
DC Power Ports
HV Impulse
AC Power Ports
5 kV
Signal ports 2 kV
DC Power Ports 1.5 kV
Dielectric Strength
AC Power Ports 2 kV
Signal ports ± 4 kV @ 2.5 kHz
DC Power Ports
Fast Transient
AC Power Ports
± 4 kV