EasyManua.ls Logo

Siemens RVA53.242 - Locking Signal Gain

Siemens RVA53.242
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
109/218
Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Description of heating engineer settings 26.03.2001
No adaption (range ):
At attenuated outside temperatures above 12 °C, the heating curve will not be
adapted.
Example using a nominal room temperature setpoint of 20 °C.
0
2371D07
TA
12 4 -4 -12
0,5
1
f
20
ged
f1
f2
ZAF1 ZAF2
f Factor
f1 Factor for parallel displacement
f2 Factor for slope
TAged Attenuated outside temperature
ZAF1 Adaption sensitivity 1 (line 39
OE M
)
ZAF2 Adaption sensitivity 2 (line 40
OEM
)
4.47 Locking signal gain
Matching the system to different types of boilers and plant conditions.
The locking signal gain is a final adjustment of the locking signal which leads to a
restriction of the mixing valve. It is the result of a number of integrals such as shifting
d.h.w. priority.
Setting range Unit Factory setting
0...200 % 100
The gain is adjustable between 0 % and 200 %. The setting changes the response of
the mixing heating circuits to restrictions imposed by locking signals, but not that of the
other consumers. Also refer to "mixing valve restriction" in Index.
Setting Response
0 % Locking signal will be ignored
1...99 % Locking signal will be considered as a reduced
signal
100 % Locking signal will be adopted unchanged
101...200 % Locking signal will be considered up to twice the
normal signal
Diagram
Benefit
Description
Setting
Effect
Example

Table of Contents

Related product manuals