Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Description of OEM settings 26.03.2001
5.3 Switching differential of the boiler temperature
Matching the burner to the type of boiler.
The boiler temperature is controlled by a 2-position controller for which a switching
differential can be set.
Setting range Unit Factory setting
0...20 °C (K) 8
The setting changes the switching differential of the boiler temperature control.
Entry:
Increase: Switching differential will become wider
Fewer burner starts and longer burner running times
Decrease: Switching differential will become smaller
More burner starts and shorter burner running times
With 2-position control, heat is produced at certain intervals. The period of time during
which heat is delivered is dependent upon the boiler mass and the amount of water
contained in the boiler.
The greater the demand for heat, the longer the burner runs at a time.
°C
2371Z23
ON
OFF
w
SD
w Setpoint
SD Switching differential of the boiler
Switch-on point
Switch-off point