Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Description of end-user settings 26.03.2001
3.15 Switching times of time switch program 3
(d.h.w.)
This is the setting of the switching times for d.h.w. time switch program at which the
d.h.w. temperature setpoint will change.
The time switch program thus set is activated by pressing the d.h.w. operating mode
button .
Setting range Unit Factory setting
- -:- -...24:00 h : min See "Program overview"
below
First, select the weekday for which the switching times shall be entered!
The controller then makes a check to ensure the entries have been made in the correct
order.
At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times the setpoints will be activated.
Entry:
– – : – – Switching point inactive.
00:00...24:00At the time entered, heating to the respective temperature is ensured.
Line Switching point D.h.w temperature setpoint Standard
Switch-on time period 1
Nominal setpoint
06:00
Switch-off time period 1
Reduced setpoint
22:00
Switch-on time period 2
Nominal setpoint
– – : – –
Switch-off time period 2
Reduced setpoint
– – : – –
Switch-on time period 3
Nominal setpoint
– – : – –
Switch-off time period 3
Reduced setpoint
– – : – –
Description
Setting
• • •
Important
Note
Effect
Program overview