5.15 Switching differential of damper actuator
Setting the switching differential for 2-position control of the damper actuator.
Adjustable switching differential for burner control.
Setting range Unit Factory setting
0...20 °C (K) 2
The setting changes the switching differential of air damper control.
Entry:
Increase: Switching differential becomes wider.
Fewer on / off pulses and longer intervals between full load and basic
load.
Decrease: Switching differential becomes smaller.
More on / off pulses and shorter intervals between full load and basic
load.