74/218
Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Description of heating engineer settings 26.03.2001
4.3 Display of plant type
Plant structure is easy to understand.
Straightforward checking of configuration.
Displays the plant type used.
Display Unit
0...151
The number of the current plant type will automatically be displayed on this operating
line.
Display:
0 Invalid plant configurations
1...151 Valid plant configurations
(refer to section “Plant types”)
Based on the connected peripheral devices and parameter settings, the controller
ascertains the current plant type.
The plant type is displayed in the form of a number which corresponds to the plant
diagram.
Refer to section "Application examples" for the various types of plant with the required
peripheral devices.
The following factors have an impact on the generation of the type of plant:
Connecting a d.h.w. temperature sensor to B31/H2/B41
Connecting a d.h.w. temperature sensor or thermostat to B3
Setting operating line “d.h.w. controlling element” (line 128)
Setting operating line “Output K6” (line 95) or output K7 (line 96)
Input signal at B1
Setting operating line “Heating curve slope HK1” (line 30) - or value between 2.5 and
40)
Setting operating line “Heating curve slope HK2” (line 32) - or value between 2.5 and
40)
Setting the type of heat source (line 80)
Benefits
Description
Setting
Effect
Plant type