EasyManua.ls Logo

Siemens RVA53.242 - 1.1.1 Overview of heating engineer parameters

Siemens RVA53.242
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27/218
Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Handling 26.03.2001
1.1.1 Overview of heating engineer parameters
RVA63.242
RVA53.242
Function
Range
Unit
Resolution
Factory
setting
Service values
51 51 Output test
0 Control mode according to the operating state
1 All outputs OFF
2 Burner stage 1 ON K4
3 Burner stages 1 and 2 ON K4 / K5
4 D.h.w. charging pump ON Q3/Y3
D.h.w. diverting valve OPEN Q3 / Y3
5 Heating circuit pump 1 Q2
Boiler pump ON Q2
6 Mixing valve 1 open Y1
7 Mixing valve 2 close Y2
8 Multi-functional output ON K6
9 Mult-functional output ON K7
0...9 - 1 0
52 52 Input test
0 Boiler sensor B2
1 D.h.w. sensor 1 B3
2 D.h.w. sensor 2 B31/H2
Buffer storage tank sensor 2 B31/H2
H2 B31/H2
Flow temperature sensor HK1
4 Outside sensor B9
5 Room sensor A6
6 Return sensor B7
7 Flue gas sensor B8/B6
Collector sensor B8/B6
8 Buffer storage tank sensor 1 B4
9 Display of input H1 H1
10 Display switching status input E1. E1
0...10 - 1 0
53 53 Display of plant type 1...150 - 1 -
Actual values
55 55 Actual value of flow temperature (TVx)
Input B1
0...140 °C 1 -
56 56 Actual value of boiler temperature (TKx)
Input B2/B4
0...140 °C 1 -
57 - Actual value of common flow temperature 0...140 °C 1 -
58 58 Actual value of cascade return temperature 0 ...140 °C 1 -
59 59 Actual value 1 of buffer storage tank temperature 0 ...140 °C 1 -
60 - Actual value 2 of buffer storage tank temperature 0...140 °C 1 -
61 61 Actual value 1 of d.h.w. temperature (TBWx)
(Higher temperature)
0...140 °C 1 -
62 62 Actual value 2 of d.h.w. temperature (TBWx)
(Lower temperature)
0...140 °C 1 -
63 63 Display of max. flue gas temperature (TGxmax)
To make a reset to the current value, press the + and –
buttons simultaneously for 3 seconds
0...350 °C 1 -
64 - Actual value of collector temperature (B6) 0...350 (Pt1000)
0...230 (Ni1000)
°C 1 -
65 65 Attenuated outside temperature (TAxged) -50...+50 °C 0.5 -
66 66 Composite outside temperature (Taxgem) -50...+50 °C 0.5 -
67 - Outside temperature source
- - . - - No signal
00.01...14.16 Address
- -:- / 00.01...14.16
- 1 -

Table of Contents

Related product manuals